型号LTLH 参 数 |
50S |
60S |
80S |
90S |
110S |
125S |
140S |
160S |
||
制冷量/制热量(1) |
KW |
147/165 |
193/217 |
240/270 |
291/327 |
369/415 |
427/480 |
489/550 |
550/619 |
|
104kcal |
13/14 |
17/19 |
21/23 |
25/28 |
32/36 |
37/41 |
42/47 |
47/53 |
||
制冷量/制热量(2) |
KW |
161/181 |
219/246 |
268/302 |
314/353 |
407/458 |
450/506 |
508/572 |
582/655 |
|
104kcal |
14/16 |
19/21 |
23/26 |
27/30 |
35/39 |
39/44 |
44/49 |
50/56 |
||
压缩机 |
输入功率(1) |
KW |
30/44 |
38/56 |
47/69 |
56/83 |
71/105 |
82/121 |
94/139 |
105/155 |
输入功率(2) |
KW |
40/59 |
53/78 |
64/94 |
75/111 |
96/142 |
109/161 |
121/179 |
137/203 |
|
制冷回路数 |
N。 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
冷媒种类 |
(1)R22、(2)R407C环保型复合工质 |
|||||||||
注油量 |
L |
7 |
10 |
12 |
12 |
13 |
13 |
18 |
18 |
|
R22冷媒量 |
Kg |
22 |
28 |
40 |
45 |
50 |
58 |
68 |
85 |
|
安全保护 |
过载、过流保护,安全阀,高低压保护,防冻保护,缺相逆相保护,油压差保护,水压差保护 |
|||||||||
蒸发器 |
水流量(1) |
m3/h |
25 |
33 |
41 |
50 |
63 |
73 |
84 |
95 |
压力降(1) |
Kpa |
≤60 |
||||||||
水流量(2) |
m3/h |
10 |
14 |
18 |
21 |
27 |
29 |
33 |
38 |
|
压力降(2) |
Kpa |
≤60 |
||||||||
进出水管径 |
DN |
100 |
100 |
125 |
125 |
150 |
150 |
200 |
200 |
|
冷凝器 |
水流量(1) |
m3/h |
15 |
20 |
25 |
30 |
38 |
44 |
50 |
56 |
压力降(1) |
Kpa |
≤50 |
||||||||
水流量(2) |
m3/h |
27 |
37 |
46 |
54 |
70 |
77 |
87 |
100 |
|
压力降(2) |
Kpa |
≤50 |
||||||||
进出水管径 |
DN |
100 |
100 |
125 |
125 |
150 |
150 |
200 |
200 |
|
机组尺寸 |
机组长度 |
mm |
2500 |
2800 |
3000 |
3000 |
3300 |
3500 |
3500 |
3500 |
机组宽度 |
mm |
700 |
700 |
900 |
900 |
1200 |
1200 |
1200 |
1200 |
|
机组高度 |
mm |
1300 |
1300 |
1600 |
1600 |
1650 |
1650 |
1700 |
1700 |
|
运行重量 |
Kg |
1300 |
1500 |
1600 |
1800 |
2000 |
2200 |
2500 |
3000 |
注:(1)表中的制冷量、输入功率是按以下条件:
蒸发器入出水温度12/7℃ 冷凝器入出水温度16/26℃
(2)表中的制热量、输入功率是按以下条件:
蒸发器入出水温度16/6℃ 冷凝器入出水温度45/50℃